Calibration Series: 20-Point Calibration

Calibration Series: 20-Point Calibration

5/23/2022

12-point, 15-point, and 20-point calibration share a single calibration interface; calibrating all 20 points is equivalent to using the 20-point calibration method.

This calibration method can correct the zero point. It is not recommended to use a curved welding gun for calibration.

Click the 【Twenty-Point Calibration】 button at the bottom of the “Tool Calibration” interface to enter the “Twenty-Point Calibration” interface, as shown.

20 points

The specific calibration steps are as follows:

  1. Find a reference point (the pen tip serves as the reference point) and make sure this reference point is fixed.
  2. Start inserting position points; after inserting each point, click 【Mark This Point】; insert 20 points. The greater the pose difference between each point, the better.

Manufacturer's recommendation for the calibration sequence: Point 1 with the tool pointing vertically downward; Points 2–4 moving along A+; Points 5–7 moving along A-; Points 8–10 moving along B+; Points 11–13 moving along B-; the remaining points mainly rotate the C axis, arranged in a star-shaped (asterisk-like) pattern for calibration.

The specific steps are as follows.

Point 1

Robot tool tip perpendicular to the reference point

Point 1

Point 2

From Point 1, move A+

Point 2

Point 3

From Point 1, move A+ 40 degrees

Point 3

Point 4

From Point 1, move A+ 60 degrees

Point 4

Point 5

From Point 1, move A- 20 degrees

Point 5

Point 6

From Point 1, move A- 40 degrees

Point 6

Point 7

From Point 1, move A- 60 degrees

Point 7

Point 8

From Point 1, move B+ 20 degrees

Point 8

Point 9

From Point 1, move B+ 30 degrees

Point 9

Point 10

From Point 1, move B+ 40 degrees

Point 10

Point 11

From Point 1, move B- 20 degrees

Point 11

Point 12

From Point 1, move B- 30 degrees

Point 12

Point 13

From Point 1, move B- 40 degrees

Point 13

Point 14

From Point 1, move C+ 30 degrees

Point 14

Point 15

From Point 1, move C+ 50 degrees

Point 15

Point 16

From Point 1, move C+ 70 degrees

Point 16

Point 17

From Point 1, move C+ 90 degrees

Point 17

Point 18

From Point 1, move C- 30 degrees

Point 18

Point 19

From Point 1, move C- 60 degrees

Point 19

Point 20

From Point 1, move C- 90 degrees

Point 20
Note